Applications -PVC Single cores suitable for installation for flexible use for medium mechanical stresses with free movement without tensile stress of forced movements in dry, moist and wet rooms as well as outside (fixed installation). Is not suitable to be used as direct burial-or as underwater cable. CE = the product conforms to EC Low-Voltage Directive 2006/95/EC
Core identification -Upto 5 cores: color coded according to VDE 0293-308 From 6 cores: all black core(JZ/OZ), protective conductor gn-ye in the outer most layer
Temperature Range -Ocassional flexing -5°C to +70°C fixed installation - 20°C to +70°C
Permissible operating temperature -Max. 70°C at conductor
Nominal voltage -Uo/U 06/1 kV
Test voltage -4000 V
Breakdown voltage -min. 8000 V
Insulation resistance -min. 20 MOhm x km
Minimum bending radius -flexing 20 x cable ø, Fixed installation 4 x cable ø
Cable construction
Properties